アーク長の短縮による故障アークエネルギーの低減効果
タイトル(英文)
Effect for decreasing arc energy on faults by shortening arc length
概要 (図表や脚注は「報告書全文」に掲載しております)
概要 (英文)
Many short circuit faults occurring in an electric power system accompany arc discharge.If an arc is generated in an enclosed space,it generates heat which raises the internal pressure,for lowering the reliability of equipment.Shortening the arc length is considered to be one of effective methods for decreasing the arc energy.To prevent the elongation of arc passage,a model with a metallic material such as wire netting or grating installed near cables was used for measuring the arc energy,and the following results were obtained.(1)It was confirmed that if the distance between the cables and the metallic material was shorter,the arc energy was less.(2)A flat relatively thick grating used as the metallic material gave a constant energy decrease effect during energization.A wire netting wound around a fault location exhibited a higher energy decrease effect than the grating in the beginning of the fault.(3)The above measure could decrease the arc energy to lower than one half of the conventional energy,and a prospect could be obtained on the possibility to half the heat and the resultant pressure rise.
報告書年度
1991
発行年月
1992/02/13
報告者
担当 | 氏名 | 所属 |
---|---|---|
主 |
関口 輝一 |
横須賀研究所電力部大電流研究室 |
共 |
岡崎 正幸 |
横須賀研究所電力部大電流研究室 |
キーワード
和文 | 英文 |
---|---|
配電系統 | Distribution Line |
短絡故障 | Short-circuit Fault |
アーク | Arc |
故障対策 | Fault counterm |